Electrical SafetyNovember 23, 2026

Carbon Monoxide Detectors in Ontario: Where to Put Them and What the Law Requires

Carbon monoxide (CO) is the household hazard you cannot notice on your own. Health Canada says it has no smell, taste or colour and can only be detected with a carbon monoxide alarm. That is the reason Ontario requires CO alarms in so many homes, and the rules about where they go changed on January 1, 2026.

This guide covers which Ontario homes need a carbon monoxide detector, where to install it under the current Fire Code, how the Building Code treats hardwired alarms in new construction, how to test and replace them, and what to do if one goes off. The rules come from the Ontario government's Fire Code guidance and its 2024 Building Code compendium, and the health facts come from Health Canada. The government's documents call the device a carbon monoxide alarm. Most people say carbon monoxide detector, and this guide uses both terms for the same thing.

Ontario's carbon monoxide detector law in brief

The rules for existing homes sit in Section 2.16 of Division B of the Fire Code (O. Reg. 213/07). The province's guidance for houses says a CO alarm is required when the home has a fuel-burning appliance, has a fireplace, has an attached garage, or, since January 1, 2026, is heated by air from a fuel-burning appliance that is not inside the home. Any one of those conditions is enough. A furnace or water heater that burns fuel counts as a fuel-burning appliance.

Responsibility follows ownership. In an owner-occupied home the homeowner is responsible for meeting the CO alarm requirements. In a rental home the landlord is responsible. The province also says it is against the law for anyone to remove the batteries from a CO alarm or tamper with it in any way, which applies to tenants and visitors as much as owners.

Where to install a carbon monoxide detector in a house

Since January 1, 2026, a house that meets any of the conditions above needs CO alarms in two kinds of location. The first is adjacent to each sleeping area, meaning the hallway or space just outside the bedrooms. The second is new: an alarm on every storey of the home, including storeys with no bedrooms at all.

That change raises the count in many houses. A home with its bedrooms off one upstairs hallway once met the rule with an alarm outside those rooms. Under the 2026 wording, the main floor with the kitchen and living room needs its own alarm, and so does a basement level with a furnace room and a rec room.

Health Canada makes the same point about priorities. It says the most important spot for an alarm is in hallways, outside of sleeping areas. Beyond the locations the Fire Code requires, follow the placement directions in the alarm's instructions, since the manufacturer sets those for its own device.

Where to put carbon monoxide detectors in apartments and condos

In multi-unit buildings the rules start from the suite rather than the whole house. Under the province's guidance, a suite needs a CO alarm when it contains its own fuel-burning appliance, such as a furnace or water heater, or a fireplace. A suite also needs one when it sits directly above, below or beside a service room that has a fuel-burning appliance, or directly above, below or beside a garage.

So a condo unit with electric heat and no fireplace can still need an alarm, because the building's parking garage or boiler room shares its floor, ceiling or wall. When you are unsure which rooms surround your unit, the building's management can tell you where the service rooms and garage levels are.

Hardwired smoke and carbon monoxide detectors in new homes

For existing homes the Fire Code is flexible about power. The province's guidance says CO alarms may be hardwired, battery-operated or plug-in devices. New construction is stricter. The 2024 Building Code compendium requires CO alarms installed under the Building Code to be permanently connected to an electrical circuit (Article 9.32.3.9C), and it allows battery operation only where the building has no electrical supply. Ontario's guide to building a laneway house puts it plainly: carbon monoxide alarms must be connected to an electrical circuit and located near bedrooms and sleeping areas.

The Building Code adds locations tied to garages. It calls for a CO alarm in a suite whose wall, floor or ceiling assembly is shared with a storage garage, and in sleeping rooms that share such an assembly with a garage. A bedroom built over an attached garage is one example.

The code names the standards too. CO alarms conform to CAN/CSA-6.19, Residential Carbon Monoxide Alarming Devices, and smoke alarms conform to CAN/ULC-S531. A combination smoke and carbon monoxide alarm installed to meet both rules should therefore list both standards on its label. For any alarm you buy for an existing home, the province suggests looking for the logo of a recognized testing agency, such as CSA, ULC or Intertek (ETL).

Have electrical work in mind? Get a free quote.

Licensed & Insured | ECRA/ESA 7014730

Wiring a carbon monoxide detector: when an electrician is needed

A plug-in or battery CO alarm in an existing home is something you can buy and set up yourself by following its instructions. A hardwired alarm is a different job. Connecting a new alarm to a circuit, adding alarms on storeys that never had one, or linking alarms during a renovation all change the home's wiring.

ESA says almost all electrical work must be reported with a notification of work before it starts, and it counts the repair and replacement of devices on existing wiring as renovation work. Homeowners may do electrical work in their own home after filing that notification and having ESA review it, but friends, family and handymen cannot do it for them, and anyone you hire must hold an ECRA/ESA licence.

When KV Bear Electrical (ECRA/ESA 7014730) wires a renovation or a secondary suite, the alarm wiring is planned with the rest of the circuits and the ESA notification covers it. If you are planning work like that, call 905-999-5048 or request a quote.

How CO alarm rules sit alongside smoke alarm rules

Ontario treats smoke alarms and CO alarms as two separate requirements, and a home that needs both has to meet each of them. The province says it is the homeowner's responsibility to install and maintain smoke alarms on every storey and outside sleeping areas, and that rule reaches every Ontario home, cottage, cabin and seasonal home, whether or not anything in it burns fuel. The CO requirement, by contrast, depends on the fuel-burning appliance, fireplace, attached garage or outside heat source described earlier.

Since January 1, 2026 the two sets of locations line up more closely in a typical house, because both now call for an alarm on every storey as well as outside the sleeping area. That makes combination smoke and CO alarms a practical choice for many owners, provided each unit carries the right certification for both jobs.

New construction ties the two together through the wiring. The Building Code requires the smoke alarms in a dwelling unit to be permanently connected to a circuit with no disconnect switch, and to be wired so that one alarm sets off all of them when more than one is needed. CO alarms in new homes are connected to an electrical circuit as well. If you are building a home or adding a suite, ask your electrician to plan both sets of alarms on the same drawings.

Testing, batteries and replacement

The province says you must keep a CO alarm in operating condition. Its guidance is to test each alarm every month by pressing the test button, replace the batteries every year, and replace the alarm according to the manufacturer's instructions. Smoke alarms have a fixed 10 year replacement guideline in Ontario's fire safety advice, but CO alarm lifespans are set by each manufacturer, so the instructions that came with your unit decide when it is due.

Landlords carry extra testing duties. The province lists testing CO alarms in rental units annually, when the battery is replaced, when changes are made to the electrical circuit, and when there is a change of tenancy. The third trigger matters for anyone renovating a rental unit: once electricians have worked on the circuit, the alarm gets tested again.

What to do if your carbon monoxide detector goes off

Treat a sounding CO alarm as an emergency. Health Canada's direction is to leave the home immediately and get into fresh air without trying to find the source. Once outside, call 9-1-1, your local fire department or emergency services, and go back in only after a professional has fixed the problem.

Know the symptoms as well, because they are easy to mistake for a cold or the flu. Health Canada lists headache, shortness of breath, fatigue, dizziness and nausea among the effects of exposure, with chest pain, poor vision and difficulty thinking at higher levels. A working alarm in the right places is what warns you before those symptoms build.

A quick checklist for an Ontario home

Start by deciding whether your home is covered. Look for a fuel-burning furnace, water heater or other appliance, a fireplace, an attached garage, or heat that comes from a fuel-burning appliance outside your home. If any of those apply, plan for an alarm outside each sleeping area and one on every storey.

Next, check what you already have. Press the test button on each alarm, note any that are past the replacement date in their instructions, and change the batteries if they are more than a year old. If your home was built recently and the alarms are wired, leave the wiring alone and replace like with like, following the manufacturer's directions.

Finally, if a renovation, a basement finish or a new suite is on the way, put the alarms into the electrical plan from the start. That is far easier than adding wired alarms after the drywall is up.

Frequently Asked Questions

Is a carbon monoxide detector required in every Ontario home?

No. Under the Fire Code a house needs one when it has a fuel-burning appliance, a fireplace or an attached garage, or, since January 1, 2026, when it is heated by air from a fuel-burning appliance outside the home. A house with none of those is not covered by the requirement.

How many carbon monoxide detectors does a house need now?

In a house the rules cover, at least one adjacent to each sleeping area and, since January 1, 2026, one on every storey, including storeys without bedrooms. One alarm can serve both purposes on a storey where it sits outside the bedrooms.

Can a carbon monoxide detector be plug-in or battery operated?

In an existing home, yes. The province's Fire Code guidance allows hardwired, battery-operated or plug-in CO alarms. Alarms installed under the Building Code in new construction must be permanently connected to an electrical circuit, with battery power allowed only where there is no electrical supply.

Who installs carbon monoxide alarms in a rental unit?

The landlord. The province says landlords are responsible for the CO alarm requirements in rental homes and must test the alarms annually, after a battery change, after changes to the electrical circuit and at a change of tenancy. Nobody may remove the batteries or tamper with the alarms.

Published by KV Bear Electrical

KV Bear Electrical Inc. is a licensed residential electrical contractor (ECRA/ESA 7014730) based in Oshawa, Ontario. The facts here come from the official sources listed above. Have a question about your home? Call 905-999-5048.

Have a Question? Get a Free Quote

ECRA/ESA 7014730 | Licensed & Insured

Get Your Free Quote Today

Prefer to talk? Call us.

By submitting this form, you agree to receive email from KV Bear Electrical about your request. You can ask us to stop at any time.